SD-805 Smart Transmitter / Gas Detector

For combustible and toxic gases. ATEX and MED approved (Wheelmark)

 

Aktuelles Datenblatt

SD-805

The model SD-805 series smart transmitter/detector heads are state of the art instruments housed in a flameproof enclosure.
A simple magnetic control key is placed over clear marked positions on the surface plate to test and adjust the instrument without opening the transmitter/detector head.
Two different detection principles are provided with SD-805 series which enable you to select the most suitable principle according to detection gas, range and application for use. Especially, the Model SD-805RI can detect combustible gases (CH4 and i-C4H10) with 0-100% vol F.S. in inert gas base.
Dual alarm contacts and trouble alarm contact are provided for activation of external buzzer or alarm light. Powered by 24 VDC, the unit has a 4-20 mA output for communication to outside controllers, for external readouts or alarming devices
An extensive range of accessories supplied by RKI rounds up Model SD-805 series.

Features:

  • For combustible and toxic gases
  • Longlife RKI sensors
  • Dual alarm contacts
  • 4-20mA linear output
  • Automatic zero correction function, self-diagnosis
  • Explosion proof housing, IP65 ingress class
  • ATEX and MED approved (Wheelmark)

Detection gas

Lower Explosive Limit (LEL)

Detection range

Resolution (digit)

Methane

CH4

5,0% Vol.

0-100% LEL

0,5% LEL

0-100% Vol.

0,5% Vol.

Ethylene

C2H4

2,7% Vol.

0-100% LEL

0,5% LEL

Ethane

C2H6

3,0% Vol.

0-100% LEL

0,5% LEL

Propane

C3H8

2,0% Vol.

0-100% LEL

0,5% LEL

Iso-Butane

i-C4H10

1,8% Vol.

0-100% LEL

0,5% LEL

0-100% Vol.

0,5% Vol.

n-Hexane

n-C6H14

1,2% Vol

0-100% LEL

0,5% LEL

IPA

C3H8O

2,0% Vol

0-100% LEL

0,5% LEL

Toluene

C7H8

1,2% Vol

0-100% LEL

0,5% LEL

MEK

C4H8O

1,8% Vol

0-100% LEL

0,5% LEL

Ethyl alcohol

C2H5OH

3,3% Vol

0-100% LEL

0,5% LEL

Model

SD-805RI

SD-805SC-RI
mit GD-A45RI

SD-805RID

SD-805EC

Detection gas
Refer to detection gas list

Carbon Monoxide (CO) in air

Hydrogen Sulfide (H2S) in air
Sampling method

Diffusion sampling

Sampling drawing

Diffusion sampling

Detection principle

Infrared sensor (NDIR)

Electrochemical sensor

Detection range

Refer to detection gas list

0~150 ppm

0~30 ppm

External output

Alarm contact

Gas Alarm:     Normally open or normally closed for
1st and 2nd alarms

Trouble alarm:     Normally open or normally closed

Remarks:     Specify either alarm contact when ordering

Gas Alarm:     Normally open or normally closed for
1st and 2nd alarms

Trouble alarm:     Normally open or normally closed

Remarks:     Specify either alarm contact when ordering

Signal trans-mission

Gas concentration:     4-20mA (linear, resistance load
below 300Ω)

Malfunction:     0.5mA

Service:    2.5mA (max. 22mA with limiter)

Gas concentration:     4-20mA (linear, resistance load
below 300Ω)

Malfunction:     0.5mA

Service:    2.5mA (max. 22mA with limiter)

Display

digital LCD-Display with backlight (One-Man-Calibration with magnetic control key)

Applicable cable

Max. 2.0 km

Power requirement

3-core 24VDC ± 10% (Max. 4W)

3-core 24VDC ± 10% (Max. 2.5W)

Structure

Flame proof Exd II BT6 approved by Baseefa

Flame proof Exd II BT4X approved by authority of Japan

Ingress class

IP65

Pending

Operating conditions

-10°C ~ +40°C, below 95% R.H. (non-condensing)

Dimensions
and weight

Ca. 124 x 233 x 115 mm, 3.5 kg,
SD-805RID approx. 4.0 kg

Accessories

Standard:     sun shade cover, fuse (1A), magnetic control key

Optional:     box type drip proof cover, pole stand, u-bolt for pole stand mounting, calibration kit,
round type splash guard cap with bump gas check function

Specifications subject to change.