RM-TC8

Gas Detection Control Unit for

8 Transmitters / Gas Sensors

 

Aktuelles Datenblatt

RM-TC8

The RM-TC8 is a compact and easily understandable system for up to eight transmitters. Due to its interfaces it is easy to integrate in even higher control and management systems.
You are free to choose between 4 different types:

RM-TC 8X
W - Wall mounted housing
R - 19‘‘ Rack control panel
S - Control panel
H - DIN-Rail

Features

  • Gas Detection Control Unit for measurement of flammable and/or toxic gases as well as oxygen
  • Graphic display
  • 8 channels, 3 alarm levels per channel
  • 24 freely programmable relays
  • 8 analogue outputs
  • Various installation types

 

 

Model

RM-TC8

Number of Transmitters

1 to 8 (4-20 mA/RS 485)
Signal Evaluation

Microcontroller with A/D-Converter

Alarm / Fault / Indication

  • Illuminated graphic display (240 x 64) for indication of measured values, messages and alarms
  • 24 (3 x 8) red LED for alarm indication
  • LED for fault indication (yellow, channel: 8 x, control unit: 1 x), operation (8 x green) and maintenance mode (1 x yellow)
Alarm Levels
3 freely adjustable alarm levels per channel, latching function configurable

Relays

  • 24 potential free change-over contacts 230 V / 5 A (total rated current: max. 10 A), freely configurable to alarm 1 to 3 and fault
  • 2 potential free change-over contacts 230 V / 5 A for maintenance mode and fault of control unit

Additional Features

  • RS 232/RS 485-interface for communication to periphery (PC or PLT-system)
  • Service function (maintenance mode)
  • Horn reset
  • Alarm reactivation
  • 4 digital inputs, potential free
  • 8 analog outputs 4-20 mA / 0-5 V / 0-10 V, potential free

Operation temperature

-10 °C to +40 °C

Installation

Wall mounted housing

DIN-Rail

19’’-Rack control panel
(5 HE x 60 TE)

Control panel

Dimensions

234 x 300 x 160 mm

234 x 300 x 170 mm

216 x 305 x 160 mm

234 x 364 x 160 mm

Material

Housing ABS

-

-

Enclosure Rating

IP 54

IP 20

IP 54 (front side)

Cable Gland

  • 1 pc. M20 x 1,5 (diameter of cable 7-13 mm)
  • 15 pcs. M16 x 1,5 (diameter of cable 5-10 mm)

-

Power Consumption

Max. 0,2 A / 45 W

Storage Temperature

-25 °C bis +60°C

Power Supply

230 V (85...264 V AC, 47...440 Hz oder 120...340 V DC)

EC-Directives

II (3)G
94/9/EC (ATEX), 89/336/EEC (EMC), 73/23/EEC (LVD)

Measuring Function

Designed according to:

  • EN 61779-1 to EN 61779-4
  • EN 4554-1 to EN 4554-3
  • EN 50104

Specifications subject to change.