RM 590

Multi-channel gas monitoring system

 

Aktuelles Datenblatt

RM-590

RM-590

The RM-590 series belongs to RKI’s family of display units. The device consists of two parts: an indicator/alarm unit and a buzzer unit.
With the help of this components, the task of multipurpose gas detection can be carried out reliably at any industry site. The multichannel gas monitoring system RM-590 can be set in most different fields very well. Typical applications for the device are petrorefinery and petrochemical plants, the semiconductor manufacturing industry, power stations, gas facilities, iron and steel works, shipping industry and many more.

Features:

  • Multi-channel gas detection and alarm system
  • Bright 4 digit LED display
  • Compact design, easy plug-in type module
  • 4-20 mA output
  • Network option available
  • Wide range of detectable gases and detector heads

RM-590The RM-590 series is to be used best in connection with RIKEN KEIKI gas detectors and allows the check of inflammable and toxic gases, as well as the check of the oxygen concentrations.
The indicator unit of the RM-590 is equipped with a four-digit digital display and 4-20mA signal output with a power consumption between 5 to 10 VDC (12 to 17 VAC).

In order to be able to deal with individual demands in the best way it is possible to tune the two alarm limit values independently. Furthermore, alarm situations can be simulated with the help of test functions without having to disconnect a plant for this case.
Besides the fact that the device is network-compatible, it is equipped with a zero point suppression function and accepts flow failure alarm.
Because of the innovative and compact design, the alarm unit can be fitted easily without wasting expensive space.

Model

GP-591

NC-591

GH-591/H

SP-591

EC-592

OX-591

OX-592

RM-592 /
RM-593

Gas detected

Combustible gases

Combustible/toxic gases

Toxic gases

Oxygen

4-20mA

Detection range

0-100% LEL

0 - a couple
thousand ppm

0 - a couple
hundred/thousand ppm

Depends
on gas

0-5, 10, 25,
or 50% vol

-

Detection principle

Catalytic
Combustion

Ceramic

Semi-
conductor

Catalytic/
semi-
conductor

Electro-
chemical

Galvanic cell

General
measuring
signal

Display

4 digit digital LED (7 segments), gas concentration indication

Alarm indication

1st Alarm: orange LED flashing

2nd Alarm: red LED flashing

Trouble alarm: green LED flashing

Alarm limits

Depends on gas

Features

  • Accepts flow failure alarm
  • Zero suppression function (maintenance mode function)
  • Easy plug-in type module
  • User selectable alarm functions, alarm test functions
  • Wide range of detectable gases and detector heads

Operation temperature
and humidity

0 - 40°C, 10 ~ 90% RF (non-condensing)

Cable

Max. 1.25 km

Max. 600m

Max. 1.25 km

Output

4-20 mA DC

Power consumption

10 W (DC)
17 VA (AC)

10 W (DC)
18 VA (AC)

5 W (DC)
10 VA (AC)

5 W (DC)
12 VA (AC)

Power supply

Single: 24 VDC (± 10%)
Multi: 100/110/115 VAC or 200/220/240 VAC

Accessoires

Power supply, buzzer unit (TAN-590), single- or multi-unit case

Specifications subject to change without notice.