This innovation bundles our reliable and long-life sensors with convenience to have all calibration- and sensor-specific data stored in nonvolatile memory within the sensor. They can conveniently be calibrated separate from the transmitter, requiring neither transport of calibration gases to the field location nor long downtime during maintenance.
Warranty is 2 years with several years expected life time.

Pyrolizer
GD-70D with pyrolizer unit PLU-70 for NF3 and TEOS mounted to condition the sample and break it down into smaller chemical constituents. This is the most reliable detection method available.
|
Modell
|
PLU-70
|
|
Applikation
|
NF3/TEOS gases detected in air
|
|
Power LED
|
Normal: LED on
Warming-up: Flashing every 1 sec interval
Trouble: Flashing at every 0.2sec interval
|
|
Self-diagnosis
|
Pyrolizer unit trouble
Fan trouble
System trouble
|
|
Power requirements
|
DC24±10%, approx 25W (Max)
|
|
Dimensions & weight
|
70(W) x 120(H) x 150(D) mm, approx. 1.2 kg
|
|
Enclosure Rating
|
IP 30
|
|
Mounting
|
Wall-mounting base plate
|
|
Sampling tubing
|
4x6mm PTFE tubing recommended. PP half union fittings provided as standard accessories
|
|
Cable gland
|
1.25sq 2 core cable for power supply DC24V
|
All Specifications subject to change without notice.

Features
- For 4 years
- No additional costs within service time
- Prolongation possible
Service content
Complete maintenance, change of sensors, filters and batteries, preventive service, calibration with test gas, test of all electric functions, test of alarm points, check of pneumatic units, test report, worldwide supply network
|
Model
|
GD-70D
|
GD-70D-NT
|
GD-70D-ET
|
|
Communication
|
4-20mADC
|
DC power line communication
|
PoE (Power over Ethernet)
|
|
Detection principle
|
Different type depending upon sensor (see gas table for sensor types and detectable gases)
|
|
Sampling method
|
Sample-drawing (auto-adjustment of low rate) 0.5ℓ / min±10%
|
|
Display
|
Large LC-display (white backlight), digital & bar chart display of gas concentration
Flow rate, communication status, pyrolizer, gas detected
Error code, error message
1st alarm : Red 2nd alarm : Red Fault alarm : Yellow Operation : Green
|
|
External output
|
1st alarm/2nd alarm/Trouble alarm : Relay contact output for each alarm
|
|
Self-diagnosis
|
System failure, sensor failure, flow failure, communication failure (NT/ET)
|
|
Data logging
|
Event history, alarm history, calibration history
Alarm trend (180 sec before/after 1st alarm)
|
|
Operating temp. & humidity
|
0-40°C, 30-70%RH (non-condensing)
|
|
Operational settings
|
All operational settings are user adjustable on front panel
|
|
Power requirements
|
DC24±10%, approx 1.5W (max 4W including sensor unit)
Note: Approx 2.5W (Max 5W) with SGU sensor unit
|
PoE (Power over Ethernet) standard arrangement
|
|
Dimensions & weight
|
70(W) x 120(H) x 150(D) mm, approx 0.9kg including sensor unit
|
|
Enclosure Rating
|
IP 30
|
|
Mounting
|
Wall-mounting base plate
|
|
Sample tubing
|
4x6mm PTFE tubing recommended. PP half union fittings provided as standard accessories
|
|
Cable gland
|
Cable type varies depending on communication method (cable bushing optional)
|
All Specifications subject to change without notice.